|

|
|

42213 Sarah Way, Temecula, CA 92590,
USA |
Tel: 800-854-8530 (USA)
Tel: 951-699-2437
Fax: 951-695-7246
sales@electronumerics.com |
 |
Micro Series
Dual-Setpoint Controller
Options
With contact or solid state relays,
selectable control modes

Dual 8A relays |

Dual solid state relays |

Features
- Applicable to all Micro Series digital
panel meters, counters, timers
- Isolated dual-channel contact or
solid state relay versions
- Form-C contact relays rated
8A
at 250 Vac or 8A at 24 Vdc
- Solid state relays rated 120 mA
at 125 Vac or 250 mA at 0-150 Vdc.
- Outputs derived from filtered or
unfiltered signal input
- Fast response time
- Selectable output time delay
- Multiple
operating modes
- output above or below setpoint
- latching or non-latching
- band deviation or hysteresis around each setpoint.
- Setpoint setup via front panel
pushbuttons or RS-232/485
- Security lockout of front panel
setpoint controls
|

Description
Contact Relays or
Solid State
Two optional plug-in setpoint controller
boards are available to add control and alarm capability to Micro DPMs, counters and
remote displays:
Operating Modes
Operation above or below setpoint.
Each relay may be individually programmed to be energized above or below a setpoint, or
may be disabled.
Latching or non-latching.
Each relay may be individually programmed to operate in a latching or non-latching mode.
In the latching mode, when an alarm or shutdown condition is reached, the output remains
in the alarm condition until it is reset by front panel pushbuttons, via the serial
interface, or via the rear connector. In the non-latching mode, the output is
automatically reset when the alarm condition no longer exists.
Band deviation mode. Each
relay may be set to operate in a band deviation mode, where an alarm is generated whenever
the reading is a specified number of counts above or below the setpoint. In particular,
band deviation is ideal to flag an out-of-tolerance condition.
Hysteresis mode. Each relay
may be set to operate in a hysteresis mode, where turn-on occurs at a specified amount
above the setpoint and turn-off occurs at the same amount below the setpoint.
Filtered or unfiltered input.
Relay action may be derived from either the filtered or unfiltered DPM input signals.
Using the unfiltered signal improves response time, which is typically 17 ms for a DPM
with the solid state relay board. Fast response time is one of the major strengths of
Micro DPMs, which can digitize analog data as often as 60 times per second. Using the
filtered input reduces the chance of alarm triggering due to noise.
Provisions for signal noise.
A programmable time delay and reduction of relay chatter can be achieved in the DPM by
selecting 1 to 128 readings in binary steps (20 ms to 2 s) prior to updating the output.
Snubber circuitry is part of the contact relay board to prolong contact life. The relay
response time of counters is controlled by a selectable gate time from 10 ms to
199.99 s.
Setup
Setpoint values and deviation bands are easily
entered via front panel pushbuttons or by computer via the serial interface. Security
lockout of the front panel pushbuttons may be set to allow operators to view but not
change setpoint values. Front panel push-button operation can also be completely disabled.
The
Micro Weight Meter and
Batch Controller offer setpoint control modes beyond those of normal meter or counter operation.
|

Specifications
|
Operation |
Power
Update Rate
Setup
Operating modes
Lockouts
Input Filtering
Time Delay |
Provided
by meter.
60 Hz or 50 Hz
Front panel pushbuttons or RS-232/485.
Available for each output: operate above or below setpoint, latching or non-latching, band deviation mode around
setpoint, hysteresis mode around setpoint, disabled.
May be set to allow display and change of setpoint by front panel pushbuttons, allow
display only by alarm pushbutton, or disable pushbuttons.
Setpoint compared to either filtered or unfiltered signal.
Programmable from 1 to 128 readings. |
|
Alarm
Status Indication |
Type
Lamp Lit |
Two red LED
lamps
When relay is energized |
|
Environmental |
Operating
Temperature
Storage Temperature
Relative Humidity |
0°C to 60°C
-40°C to 85°C
95% at 40°C, non-condensing |
|
Contact
Relay Version |
| Power Rating |
AC Load
DC Load |
8A at 250 Vac
8A at 24 Vdc |
| Isolation to Signal &
Meter Ground |
Isolation Group
Rated Voltage
Withstand Voltage |
C
250 Vac
4.2 kVp for 1 min |
| Response Time to Input Signal |
DPM Pickup Time
DPM Release Time
Counter Pickup or Release time |
26
ms typ (unfiltered)
22 ms typ (unfiltered)
Gate time +30 ms +2 periods max |
|
Solid
State Relay Version |
| Power Rating |
AC loads
DC loads |
120 mA at
125 Vac, 20 ohms series resistance.
2 loads, 250 mA, 0-150 Vdc peak hold-off, 5 ohms series resistance.
4 loads, 120 mA, 0-150 Vdc peak hold-off, 10 ohms series resistance. |
| Isolation to Signal &
Meter Ground |
Isolation Type
Safety Rating |
Optical
250 Vac, 4.2 kVp per High Voltage Test |
| Response Time to Input Signal |
DPM
Counter |
17
ms typ (unfiltered)
Gate time + 30 ms + 2 periods max |

Setpoint Operating
Modes
Normal, Non-Latched Operation |
 |
In this mode, the relay closes when the reading rises
above the setpoint and opens when the reading falls below the setpoint. Relay ON/OFF
control action is independently programmable for each of the two relays and can be
reversed through a setup command. |
Latched Operation |
 |
The relay stays actuated until reset externally. This mode
can be used to shut down machinery or a process when an operating limit has been exceeded,
or to maintain an alarm until acknowledged by an operator when the alarm condition has
passed. |
Mixed Latched and Non-Latched Operation |
 |
One of the relays can operate in a
non-latched mode, for instance to turn off a heater when an operating temperature setpoint
is reached. The other relay can operate as a latching fail-safe backup and turn off the
entire process when a second, higher setpoint is reached, indicating a malfunction. |
Deviation Mode Operation |
 |
A deviation limit (50 in this example) is
set up around both sides of the setpoint. The relay closes (or opens) when the reading
falls within the deviation band, and opens (or closes) when the reading falls outside of
this band. This mode sets up a passband around the setpoint and is often used for
component testing. |
Wide Hysteresis Mode Operation |
 |
In this example, a hysteresis limit of 600
is set below the setpoint. The relay closes when the reading reaches a lower limit (the
setpoint less hysteresis) and opens when the reading reaches an upper limit (the
setpoint).
One application is automatic tank filling. A fill operation is
automatically initiated when the tank level has reached a lower level and is terminated
when the level has reached an upper level. |
Narrow Hysteresis Mode Operation |
 |
Hysteresis can be used to minimize the
number of ON/OFF control cycles around a setpoint, thereby increasing the life of motors,
relays, etc.
A very narrow hysteresis band (such as 5 counts) can also be used to
minimize relay chatter around a setpoint due to electrical noise on the signal, or due to
signal feedback caused by load switching. The hysteresis limit should exceed the noise
amplitude. |

Electrical
Connections
 Dual
contact relays
Each load load rated 8A at 250 Vac
or 8A at 24 Vdc. |

Solid state, AC or bidirectional DC
connection with 2 loads
Each load rated 120 mA at 125 Vac, or 120 mA at 150 Vdc, 20 ohms series resistance. |
 Solid state, DC
connection with 4 loads
Each load rated up to 120 mA at 150 Vdc,
10 ohms series resistance. |

Solid state, DC connection with 2
loads
Each load rated up to 250 mA at 150 Vdc,
5 ohms series resistance. |

Micro & Mighty Series Downloads
|